Page 67 - UNITRO Alarm Annunciators
P. 67

Connection diagram ME 24-P logic
                                       (PSC- and Standard-version)





























            Technical data:
            1.   Type of construction:                            10.  Resolution:
                 control board housing aluminum                        ≥ 1ms (opto-mos) (in preparation)
                 144 x 144 x 160 + 25mm                                ≥ 10ms (relay)
                 (cutting for installation 138 x 138 + 1mm)       11.  Switch-on delay:
            2.   Degree of protection:                                 programmable from 50ms to 10min
                 front: IP50, with full-view                           (in steps of 50ms, 2s and 1min)
                 acrylic glass doors IP54                         12.  Minimum signal duration:
                 housing: IP20                                         1ms
            3.   Weight:                                          13.  First-up discrimination:
                 max. 1750g                                            1ms
            4.   Climatic conditions:                             14.  Flashing frequencies:
                 in accordance with UNITRO-PSC-Standard                2Hz / 0.5Hz
            5.   Connection:                                      15.  Power loss:
                 screw-type terminals (PSC version) or screw-type      max. 6W + 24x 0.5W
                 terminals/ plug connection max. 2.5 mm²
                                                                  16.  Relay outputs:
            6.   Supply voltage:                                       max. 5A 250V AC,
                 24V AC/DC                                             3A 30V DC
                 48-60V AC/DC
                 110/125V AC/DC                                   17.  Contactless signal outputs:
                                                                       opto-mos switch max. 300V DC, 100mA
                 220/240V AC/DC                                        (in preparation)
                 voltage-adapted
                                                                  18.  Parameterization interface:
            7.   Alarm signal nominal voltage:                         Mini USB interface for parameterization
                 24V AC to 230V AC                                     with software, used with Windows 7 Pro
                 24V DC to 240V DC                                     or higher
                 voltage-adapted, voltage tolerance ±10%
                                                                  19.  Leakage distances and clearances:
            8.   Input level for signal inputs:                        in accordance with
                 at            24V AC / DC 8mA                         UNITRO-PSC-Standard
                 at                230V AC 7mA
                 at                 60V DC 4mA                    20.  EMC, immunity to interference:
                 at           110 / 125V DC 3mA                        UNITRO-PSC-Standard, immunity higher
                 at                240V DC 2mA                         degrees of severity according to the
                                                                       actual generic standards DIN EN 61000
            9.   Data retention in the absence of power:
                 20 years

                                                      subject to change                                 Page 76