Page 59 - UNITRO Alarm Annunciators
P. 59
Connection diagram ME 8-P logic
opto mos relay output 2-pole
Technical data:
1. Type of construction: 10. Resolution:
control board housing 72 x 144 x 160 + 25mm ≥ 1ms (opto-mos)
(cutting for installation 66 x 138 + 1mm) ≥ 10ms (Relay)
2. Degree of protection: 11. Switch-on delay:
front: IP50, with full-view programmable from 50ms to 10min
acrylic glass doors IP54 (in steps of 50ms, 2s and 1min)
housing: IP20 12. Minimum signal duration:
3. Weight: 1ms
max. 800g 13. First-up discrimination:
4. Climatic conditions: 1ms
in accordance with UNITRO-PSC-Standard 14. Flashing frequencies:
5. Connection: 2Hz / 0.5Hz
screw-type terminal/ plug-in connection 15. Power loss:
or plug connection terminals max. 2.5mm² max. 6 W + 8x 0.5W
6. Supply voltage: 16. Relay outputs:
24V AC/DC max. 5A 250V AC,
48-60V AC/DC 3A 30V DC
110/125V AC/DC
220/240V AC/DC 17. Contactless signal outputs:
voltage-adapted opto-mos switch max. 300V DC, 100mA
7. Alarm signal nominal voltage: 18. Parameterization interface:
24V AC to 230V AC Mini USB interface for parameterization
24V DC to 240V DC with software, used with Windows 7 Pro
voltage-adapted or higher
voltage tolerance ±10% 19. Leakage distances and clearances:
8. Input level for signal inputs: in accordance with UNITRO-PSC-Standard
at 24V AC / DC 8mA 20. EMC, immunity to interference:
at 230V AC 7mA UNITRO-PSC-Standard; immunity higher
at 60V DC 4mA degrees of severity according to the
at 110 / 125V DC 3mA actual generic standards DIN EN 61000
at 240V DC 2mA
9. Data retention in the absence of power:
20 years
subject to change Page 68