Page 49 - UNITRO Alarm Annunciators
P. 49
Connection diagram WA 40 (M)
Technical data:
1. Type of construction: 10. Resolution:
control board housing 288 x 144 x 120 + 25mm ≥ 10ms (relay)
(cutting for installation 282 x 138 + 1mm)
11. Switch-on delay:
2. Degree of protection: programmable from 50ms to 10min
front: IP50 (in steps of 50ms, 2s and 1min)
housing: IP20
12. Minimum signal duration:
3. Weight: 10ms
WA 40 (M) max. 2600g
13. First-up discrimination:
4. Climatic conditions: 10ms
in accordance with
UNITRO-PSC-Standard 14. Flashing frequencies:
2Hz / 0.5Hz
5. Connection:
screw-type terminal/ plug-in connection 15. Power loss:
max. 20W
max. 2.5mm²
16. Relay outputs:
6. Supply voltage:
24V AC/DC or max. 2A 250V AC,
48-60V AC/DC or 0,3A 220V DC
110V AC/125V DC or
230V AC/240V DC only WA 40-M:
voltage-adapted 3x group signal outputs, changeover,
max. 2A 250V AC,
7. Alarm signal nominal voltage: 0,3A 220V
24V AC/DC or
48-60V DC or 17. Parameterization interfaces:
110/125V DC or Mini USB and NFC interface
220/240V DC or for parameterization
230V AC
voltage-adapted, voltage tolerance ±10% 18. Leakage distances and clearances:
in accordance with
8. Input level for signal inputs: UNITRO-PSC-Standard
at 24V AC / DC 8mA
at 230V AC 7mA 19. EMC, immunity to interference:
at 60V DC 4mA UNITRO-PSC-Standard, immunity higher
at 110 / 125V DC 3mA degrees of severity according to the
at 240V DC 2mA actual generic standards DIN EN 61000
9. Data retention in the absence of power:
20 years
subject to change Page 58