Connection diagram WA 40 (M)
























            Technical data:

             1.   Type of construction:                          10.  Resolution:
                  control board housing 288 x 144 x 120 + 25mm       ≥ 10ms (relay)
                  (cutting for installation 282 x 138 + 1mm)
                                                                 11.  Switch-on delay:
             2.   Degree of protection:                              programmable from 50ms to 10min
                  front: IP50                                        (in steps of 50ms, 2s and 1min)
                  housing: IP20
                                                                 12.  Minimum signal duration:
             3.   Weight:                                            10ms
                  WA 40 (M) max. 2600g
                                                                 13.  First-up discrimination:
             4.   Climatic conditions:                               10ms
                  in accordance with
                  UNITRO-PSC-Standard                            14.  Flashing frequencies:
                                                                     2Hz / 0.5Hz
             5.   Connection:
                  screw-type terminal/ plug-in connection        15.  Power loss:
                                                                     max. 20W
                  max. 2.5mm²
                                                                 16.  Relay outputs:
             6.   Supply voltage:
                  24V AC/DC or                                       max. 2A 250V AC,
                  48-60V AC/DC or                                    0,3A 220V DC
                  110V AC/125V DC or
                  230V AC/240V DC                                    only WA 40-M:
                  voltage-adapted                                    3x group signal outputs, changeover,
                                                                     max. 2A 250V AC,
             7.   Alarm signal nominal voltage:                      0,3A 220V
                  24V AC/DC or
                  48-60V DC or                                   17.  Parameterization interfaces:
                  110/125V DC or                                     Mini USB and NFC interface
                  220/240V DC or                                     for parameterization
                  230V AC
                  voltage-adapted, voltage tolerance ±10%        18.  Leakage distances and clearances:
                                                                     in accordance with
             8.   Input level for signal inputs:                     UNITRO-PSC-Standard
                  at          24V AC / DC 8mA
                  at              230V AC 7mA                    19.  EMC, immunity to interference:
                  at               60V DC 4mA                        UNITRO-PSC-Standard, immunity higher
                  at         110 / 125V DC 3mA                       degrees of severity according to the
                  at              240V DC 2mA                        actual generic standards DIN EN 61000
             9.   Data retention in the absence of power:
                  20 years