Page 27 - UNITRO Alarm Annunciators
P. 27
Connection diagrams FSB 16 + FSB 16-OUTR
Technical data:
1. Type of construction: 13. LED display:
FSB 16: FSB 16 control board housing, labeled
control board housing 96 x 96 x 85 + 25mm with marking strips:
(cutting for installation 92 x 92 + 1mm) alarm new alert: red flash light
FSB 16-OUTR: alarm acknowledge: red steady light
snap-on housing 200 x 100 x 60mm alarm removed: LED dark
2. Degree of protection:
FSB 16: status LED (power on) = green steady light
front IP50 (option IP54), rear IP20
FSB 16-OUTR snap-on housing IP20 FSB 16-OUTR snap-on housing:
power on LED:
green steady light
3. Weight: data LED: yellow flash light
FSB 16 approx. 400g data error LED: red steady light
FSB 16-OUTR approx. 500g relay contact LED: yellow
4. Climatically conditions: 14. Flashing frequencies:
in accordance with UNITRO-Standard alarms 2Hz / 0,5Hz
5. Connection: 15. Relay outputs:
screw-type terminals/ plug connection 16 full potential-free normally open contacts,
max. 2,5 mm² the input messages about software as as-
6. Front panel buttons: signed
acknowledge horn, acknowledge flash light, (assigned to Standard 1:1)
LED test (reduced by jumpers on 4 common roots)
7. Supply voltage:
24V AC/DC or 48-60V AC/DC or 2x group alarm messages and 1x horn
110/125V AC/DC or 220/240V AC/DC contact, potential-free change-over, max. con-
voltage-adapted tact conditions-carrying capacity:
8. Max. fuse: 24-250V AC, 2A / 110V DC, 0,5A /
4A medium slow 220V DC, 0,3A
9. Input level for signal inputs: 16. Parameterization:
48/60V DC -10% +15% max. 2,5mA via rear Mini USB interface
110/125V DC -10% +15% max. 2,5mA per input: running- / alarm
220V DC -10% +15% max. 2mA quiescence- / operation current
voltage-adapted switch on delay max. 10min
voltage tolerance ±10% assignment of the output contacts
10. Minimum signal duration: overall: first up / new alert
DC: 10ms 17. Leakage distances and clearances:
11. Data retention in the absence of power: in accordance with UNITRO-Standard
flash memory 18. EMC, immunity of interference:
12. Power loss 100% ED: UNITRO-Standard,
60V DC max. 4,5W in accordance with EN 61000
110V DC / 220V DC max. 5,9W
subject to change Page 36