Page 23 - LON-bus components
P. 23

Connection diagram LM 8/8R




























            Technical data:
              1.  Type of construction:                       12.  LED-display:
                  snap-on housing                                 power LED green
                  LM 16/0, 8/8-R, 0/16-R: 145 x 111 x 65mm        service LED yellow:  flashing  =  device not
                  LM 8/8-R RS485       :180 x 111 x 65mm                                          initialized
                  LM 16/8-R            2:00 x 111 x 65mm                       continuous light  =  error
              2.  Degree of protection:                           for every input and output each 1x red LED
                  IP20                                        13.  Neuron chip:
              3.  Weight:                                         3150, 10 MHz + 64kB Flash-EEPROM
                  LM 16/0, LM 8/8-R:        approx. 380g      14.  Transmission LM 16/0, 8/8-R 16/8-R, 0/16-R:
                  LM 0/16-R, 8/8-R RS485:   approx. 400g          LON FTT10A two wire (twisted-pair),
                  LM 16/8-R:               approx. 520g           78kbps, max. 2,7km
              4.  Climatic conditions:                        15.  Transmission C3 PLT:
                  in accordance with UNITRO-Standard              LON-PLT: two wire (C-band 125-145kHz)
              5.  Connection:                                     4,8kBit/s, max. 30km
                  screw-type terminals/ plug connection           in conjunction with phase coupler also
                  or spring-loaded terminals max. 2,5mm²          power line transmission on the 230/400V AC
              6.  Function buttons:                           16.  Transmission LM 8/8-R RS485:
                  reset button                                    LON RS485 two wire (twisted-pair),
                  service button                                  78kbps
              7.  Supply voltage:                             17.  Bus connection:
                  24V AC/DC, 150mA ± 10%                          isolated transceiver, 500V disconnecting
                                                                  insulation voltage
              8.  Max. fuse:
                  4A medium slow                              18.  Relay outputs:
                                                                  isolated normally open:   250V AC, 5A
              9.  Signal voltage:                                 disconnecting voltage:   2000Vrms
                  24V DC ± 10%, 4mA                               2-pin led out
                  2-pin passed out                                inductive load (contactors):
                  separation voltage 2000Vrms                     mount-in anti-interference capacitors at the coils,
                                                                  when driving roller shutter / blind motors, etc. by NO, is for
              10. Response delay:                                 an external interlock (up / down) to make!
                  25ms
                                                              19.  Leakage distances and clearances:
              11. Minimum signal duration:                        in accordance with UNITRO-Standard
                  5ms
                                                              20.  EMC, immunity of interference:
                                                                  UNITRO-Standard,
                                                                  in accordance with EN 61000

                                                      subject to change                                Page 122