Connection diagram MVL 24/0






































            Technical data:

              1.   Type of construction:                    10.  LED-display:
                   snap-on housing                               operating LED green
                   160 x 90 x 58mm high                          service LED yellow:   flashing  =  device not
                                                                                                  initialized
              2.   Degree of protection:                                       continuous light  =  error
                   IP20
                                                                 for every input 1x red LED
              3.   Weight:                                   11.  Decimal switches:
                   approx. 360g
                                                                 addressing the display modules
              4.   Climatic conditions:                          ME24 LED-LON and C3text
                   in accordance with UNITRO-Standard            without binding software,
                                                                 address on address assignment
              5.   Connection:
                   screw-type terminals/ plug connection     12.  Neuron chip:
                   max. 2,5mm²                                   3150, 10 MHz + 64kB Flash-EEPROM
                                                                 with FT-X transceiver
              6.   Function buttons:
                   reset button                              13.  Transmission:
                   service button                                LON FTT10A two wire (twisted-pair),
                                                                 78kbps, max. 2,7km
              7.   Supply voltage:
                   24V AC/DC      (=14-28V AC, 19-36V DC),   14.  Bus connection:
                   230V AC/DC     (= 85-265V AC, 85-250V DC),    isolated transceiver, 500V disconnecting
                   100mA                                         insulation voltage
              8.   Signal voltage:                           15.  Leakage distances and clearances:
                       24V DC, 5mA or                            in accordance with UNITRO-Standard
                     230V AC, 5mA                            16.  EMC, immunity of interference:
                   separation voltage 2000Vrms
                                                                 UNITRO-Standard,
              9.   Minimum signal duration:                      in accordance with EN 61000
                   5ms


                                                      subject to change                                Page 118