Page 19 - LON-bus components
P. 19
Connection diagram MVL 24/0
Technical data:
1. Type of construction: 10. LED-display:
snap-on housing operating LED green
160 x 90 x 58mm high service LED yellow: flashing = device not
initialized
2. Degree of protection: continuous light = error
IP20
for every input 1x red LED
3. Weight: 11. Decimal switches:
approx. 360g
addressing the display modules
4. Climatic conditions: ME24 LED-LON and C3text
in accordance with UNITRO-Standard without binding software,
address on address assignment
5. Connection:
screw-type terminals/ plug connection 12. Neuron chip:
max. 2,5mm² 3150, 10 MHz + 64kB Flash-EEPROM
with FT-X transceiver
6. Function buttons:
reset button 13. Transmission:
service button LON FTT10A two wire (twisted-pair),
78kbps, max. 2,7km
7. Supply voltage:
24V AC/DC (=14-28V AC, 19-36V DC), 14. Bus connection:
230V AC/DC (= 85-265V AC, 85-250V DC), isolated transceiver, 500V disconnecting
100mA insulation voltage
8. Signal voltage: 15. Leakage distances and clearances:
24V DC, 5mA or in accordance with UNITRO-Standard
230V AC, 5mA 16. EMC, immunity of interference:
separation voltage 2000Vrms
UNITRO-Standard,
9. Minimum signal duration: in accordance with EN 61000
5ms
subject to change Page 118