Page 22 - C3_series
P. 22
Fleischmann
STÖRMELDESYSTEME
C3 Main power unit
Type designation:
C3 Main power unit
DIN rail power supply unit,
primary-switched mode,
slim design,
Output: 24V DC / 1,5A
Input: 100V AC - 240V AC
Function
Supply of C3 modules via the DIN rail connector (internal bus) with a regulated 24V DC.
The electronic short-circuit and idling-proof device is connected to single-phase AC networks
with nominal voltages of 100V AC to 240V AC or to two of the phase conductors of three-phase
networks with a linked voltage of this value. In the event of a malfunction, the output voltage is
limited to 30V DC.
Operating voltage display LED green
Input data
Nominal input voltage 100V AC to 240V AC, AC input voltage range 85V AC to 264V AC,
approx. 0,75A
AC frequency range 45Hz to 65Hz
Power failure bypass > 35ms (120V AC), > 150ms (230V AC)
Output data
Nominal output voltage 24 V DC ±1 %, 1,5 A (-25 °C ... 60 °C)
Mechanical characteristics
Compact Snap-on plastic housing 35 x 99 x 95mm (WxHxD)
with DIN-rail-bus
Screw-type terminals, plug connection for connection max. 2,5mm²
Extensions
Connection in parallel for redundancy and increased capacity, maximum of 2 devices
for redundancy on DIN rail connector
Head office: Gaildorfer Str. 15 D-71522 Backnang Tel.: +49 (0)7191/141-0 Fax: +49 (0)7191/141-299
© UNITRO-Fleischmann
Office Radolfzell: Westendstr. 3 D-78315 Radolfzell Tel.: +49 (0)7191/141-150 Fax: +49 (0)7191/141-299 info@unitro.de www.unitro.de
Page 89 subject to change