Page 19 - UNITRO Alarm Annunciators
P. 19

Connection diagram FSB 24/16-24-P USB

























            Technical data:
              1.  Type of construction:                       11.  Minimum signal duration:
                  control board housing                           DC: 10ms / AC: 100ms
                  144 x 96 x 85 + 25mm                        12.  Data retention in the absence of power:
                  (cutting for installation: 138 x 92 + 1mm)      flash memory
              2.   Degree of protection:                      13.  Power loss 100% ED:
                  front IP50, rear IP20                           24V AC/DC / 60V DC           max. 4,5W
              3.   Weight:                                        110V DC / 220V DC / 230V AC  max. 5,9W
                  FSB 24/16 approx. 450g                          clocked input circuitry
                  FSB 24/24 approx. 550g                          to reduce power loss at DC
              4.   Climatically conditions:                   14.  LED display:
                  in accordance with UNITRO-Standard              labeled with marking strips
              5.   Connection:                                    alarm new alert:    red flash light
                  screw-type terminals/ plug connection           alarm acknowledge:   red steady light
                  max. 2,5 mm²                                    alarm removed:      LED dark

              6.   Front panel buttons:                           status LED (power on) = green steady light
                  acknowledge horn                            15.  Flashing frequencies:
                  acknowledge flash light                         alarms 2Hz / 0,5Hz
                  LED test
                                                              16.  Relay outputs:
              7.   External button:                               1x group alarm and 1x horn contact,
                  acknowledge horn (normally open contact)
                                                                  potential-free change-over, max. 250V 5A
              8.   Supply voltage:                                option:  group alarm, 8 outputs normally-open
                  24V AC/DC or                                        with common ground, max. 250V 5A
                  48-60V AC/DC or                             17.  Parameterization:
                  110/125V AC/DC or                               via rear Mini USB interface
                  220/240V AC/DC                                  per input:   running- / alarm
                  voltage-adapted
                                                                      quiescence- / operation current
              9.   Max. fuse:                                         switch on delay max. 10min
                  4A medium slow                                      assignment of the output contacts
              10.  Input level for signal inputs:                 overall:    first up / new alert
                    24V AC/DC    ± 10% - 15%    max.  4mA     18.  Leakage distances and clearances:
                    60V DC       ± 10% - 15%    max. 2,5mA        in accordance with UNITRO-Standard
                  110V DC        ± 10% - 15%    max. 2,5mA    19.  EMC, immunity of interference:
                  220V DC        ± 10% - 15%    max.  2mA         UNITRO-Standard,
                  230V AC        ± 10% - 15%    max.  3mA         in accordance with EN 61000
                  voltage-adapted
                  voltage tolerance ±10%

                                                      subject to change                                 Page 28