Page 11 - UNITRO Alarm Annunciators
P. 11

Connection diagram FSB 16 and FSB 48 -SA


              FSB 48
                                                   FSB 16
                             -X8 -X7 -X6 -X5        -X4                -X3        -X1
               L+  IN41        1    1    1   1       1    L+  IN1        1         1        L+
               L+  IN42        2    2    2   2       2    L+  IN2        2         2        L-
               L+  IN43        3    3    3   3       3    L+  IN3        3         3        PE
               L+  IN44        4    4    4   4       4    L+  IN4        4        -X2
               L+  IN45        5    5    5   5       5    L+  IN5        5         1
               L+  IN46        6    6    6   6       6    L+  IN6        6         2        Hupe/
                                                                                            Horn
               L+  IN47        7    7    7   7       7    L+  IN7        7         3
               L+  IN48        8    8    8   8       8    L+  IN8        8         4
               L-              9    9    9   9       9    L-             9         5        Sammelmeldung/
                                                                                            Groupalarm
                             A    A    A    A       A                  A  *        6        Hupenquittierung/
                             R   * R  * R  * R  *   R  *               R           7     L+ Horn reset
                                                                                   8        N

               *  A= Arbeitsstrom / Working current                        Im Betriebszustand Kl. 4/5 geschlossen /
                 R= Ruhestrom / Quiescent current
                                                                           In operating mode 4/5 closed


            Technical data:
              1.   Type of construction:                       11.   Input level for signal inputs:
                   control board housing                             24V AC/DC      ± 10% - 15% max. 7mA
                   96 / 192 x 96 x 85 + 25mm                         230V AC        ± 10% - 15% max. 2,9mA
                   (cutting for installation: 92 / 186 x 92 + 1mm)   for special applications with high power loss:
                                                                     60V DC         ± 10% - 15% max. 7mA
              2.   Degree of protection:                             110V DC        ± 10% - 15% max. 6mA
                   front IP50, rear IP20                             220V DC        ± 10% - 15% max. 6mA
                   (front FSB 08/16 option IP54)
                                                                     voltage-adapted
              3.   Weight:                                           voltage tolerance ±10%
                   FSB 16 approx. 400g                         12.   Power loss 100% ED:
                   FSB 48 approx. 650g                               max. 2W + 8x 1,3W
              4.   Climatically conditions:                          attention: from 60V forced ventilation
                   in accordance with UNITRO-Standard                power loss per signal:   60V DC   0,5W
                                                                       110V DC                0,7W
              5.   Connection:                                         220V DC                1,3W
                   screw-type terminals/ plug connection
                   max. 2,5mm²                                 13.   LED display:
                                                                     labeled with marking strips
              6.   Front panel buttons:                              alarm:            red steady light
                   acknowledge horn                                  no alarm:         LED off
                   LED test
              7.   External button:                                  power on LED = green steady light
                   acknowledge horn (normally open contact)    14.   Relay outputs:
              8.   Supply voltage:                                   1x group alarm and 1x horn contact,
                   24V AC/DC, 60V DC  ± 10 - 15% or                  potential-free change-over, max. 250V 5A
                   230V AC             ± 10 - 15% or           15.   Parameterization:
                   60 / 110 / 220V DC,  ± 10 - 15%                   with selector switch, in groups of 8:
                   voltage-adapted                                   quiescence- / operation current (24-110V)
              9.   Max. fuse:                                  16.   Leakage distances and clearances:
                   4A medium slow                                    in accordance with UNITRO-Standard
              10.   Minimum signal duration:                   17.   EMC, immunity of interference:
                   DC: 10ms / AC:100ms                               UNITRO-Standard,
                                                                     in accordance with EN 61000


                                                      subject to change                                 Page 20
   6   7   8   9   10   11   12   13   14   15   16