Page 11 - UNITRO Alarm Annunciators
P. 11
Connection diagram FSB 16 and FSB 48 -SA
FSB 48
FSB 16
-X8 -X7 -X6 -X5 -X4 -X3 -X1
L+ IN41 1 1 1 1 1 L+ IN1 1 1 L+
L+ IN42 2 2 2 2 2 L+ IN2 2 2 L-
L+ IN43 3 3 3 3 3 L+ IN3 3 3 PE
L+ IN44 4 4 4 4 4 L+ IN4 4 -X2
L+ IN45 5 5 5 5 5 L+ IN5 5 1
L+ IN46 6 6 6 6 6 L+ IN6 6 2 Hupe/
Horn
L+ IN47 7 7 7 7 7 L+ IN7 7 3
L+ IN48 8 8 8 8 8 L+ IN8 8 4
L- 9 9 9 9 9 L- 9 5 Sammelmeldung/
Groupalarm
A A A A A A * 6 Hupenquittierung/
R * R * R * R * R * R 7 L+ Horn reset
8 N
* A= Arbeitsstrom / Working current Im Betriebszustand Kl. 4/5 geschlossen /
R= Ruhestrom / Quiescent current
In operating mode 4/5 closed
Technical data:
1. Type of construction: 11. Input level for signal inputs:
control board housing 24V AC/DC ± 10% - 15% max. 7mA
96 / 192 x 96 x 85 + 25mm 230V AC ± 10% - 15% max. 2,9mA
(cutting for installation: 92 / 186 x 92 + 1mm) for special applications with high power loss:
60V DC ± 10% - 15% max. 7mA
2. Degree of protection: 110V DC ± 10% - 15% max. 6mA
front IP50, rear IP20 220V DC ± 10% - 15% max. 6mA
(front FSB 08/16 option IP54)
voltage-adapted
3. Weight: voltage tolerance ±10%
FSB 16 approx. 400g 12. Power loss 100% ED:
FSB 48 approx. 650g max. 2W + 8x 1,3W
4. Climatically conditions: attention: from 60V forced ventilation
in accordance with UNITRO-Standard power loss per signal: 60V DC 0,5W
110V DC 0,7W
5. Connection: 220V DC 1,3W
screw-type terminals/ plug connection
max. 2,5mm² 13. LED display:
labeled with marking strips
6. Front panel buttons: alarm: red steady light
acknowledge horn no alarm: LED off
LED test
7. External button: power on LED = green steady light
acknowledge horn (normally open contact) 14. Relay outputs:
8. Supply voltage: 1x group alarm and 1x horn contact,
24V AC/DC, 60V DC ± 10 - 15% or potential-free change-over, max. 250V 5A
230V AC ± 10 - 15% or 15. Parameterization:
60 / 110 / 220V DC, ± 10 - 15% with selector switch, in groups of 8:
voltage-adapted quiescence- / operation current (24-110V)
9. Max. fuse: 16. Leakage distances and clearances:
4A medium slow in accordance with UNITRO-Standard
10. Minimum signal duration: 17. EMC, immunity of interference:
DC: 10ms / AC:100ms UNITRO-Standard,
in accordance with EN 61000
subject to change Page 20