Page 11 - LON-bus components
P. 11
Connection diagram MVE 8/8-L
Technical data:
1. Type of construction: 14. Bus connection:
snap-on housing isolated transceiver, 500V
150 x 75 x 60 (85)mm high disconnecting insulation voltage
2. Degree of protection: 15. LED-display:
IP20 operating LED green
3. Weight: service LED yellow: flashing = device not
approx. 500g, initialized
depending on equipment variant continuous light = error
for every input and output each 1x red LED
4. Climatic conditions:
in accordance with UNITRO-Standard 16. Relay outputs MVE 0/8-L and 8/8-L:
8 isolated change-over contacts with manual
5. Connection: emergency switches: 250V AC 16A, 30V DC, 7A
hight-current screw-type terminals/ plug max. switching current: normally open: 16A
connection max. 2,5mm² normally closed: 12A
6. Function buttons: max. switching capacity: normally open: 4000VA
reset button normally closed: 3000VA
service button max. inrush current: normally open contact:
7. Supply voltage: 80A, 20ms qualified to switch max. 6 EVG
24V AC/DC ± 10%, (type OSRAM Quicktronic De Lux)
230V AC/DC (= 85-265V AC, 85-250V DC), disconnecting voltage: contact / contact 1000Vrms
150mA contact / coil 2000Vrms
8. Max. fuse: 17. Relay outputs MVE 0/8-E:
4A medium slow 8 isolated normally open contacts with manual
emergency switches: 250V AC 16A, 30V DC, 7A
9. Signal voltage: max. switching current: normally open: 16A
24V AC/DC ± 10%, 8mA max. switching capacity: normally open: 4000VA
230V AC ± 10%, 8mA max. inrush current normally open contact:
isolation by optocouplers 2000Vrms 120A, 20ms qualified to switch max. 8 EVG
10. Response delay: (type OSRAM Quicktronic De Lux)
25ms disconnecting voltage: contact / contact 1000Vrms
contact / coil
5000Vrms
11. Minimum signal duration: when driving roller shutter / blind motors, etc. by NO, is for
5ms an external interlock (up / down) to make!
12. Neuron chip: 18. Inductive load (contactors):
3150, 10 MHz + 64kB Flash-EEPROM mount-in anti-interference capacitors at the coils
13. Transmission: e.g. EMC suppression module EFS
LON FTT10A two wire (twisted-pair), 19. Leakage distances and clearances:
78kbps, max. 2,7km in accordance with UNITRO-Standard
20. EMC, immunity of interference:
UNITRO-Standard,
in accordance with EN 61000
subject to change Page 110